Please use this identifier to cite or link to this item: https://rda.sliit.lk/handle/123456789/675
Full metadata record
DC FieldValueLanguage
dc.contributor.authorHettiwatte, S. N-
dc.contributor.authorFonseka, H. A-
dc.date.accessioned2022-01-13T09:03:24Z-
dc.date.available2022-01-13T09:03:24Z-
dc.date.issued2010-
dc.identifier.urihttp://localhost:80/handle/123456789/675-
dc.description.abstract— Transpower owns and operates New Zealand’s high voltage electricity grid which includes approximately 725 in service power transformers [1]. Presently, condition monitoring of these units is routinely carried out by oil testing (moisture, acidity and dielectric breakdown) and using dissolved gas analysis (DGA), (every year), and winding resistance, insulation resistance, and bushing power factor tests (every four years). However, since the average age of a power transformer in New Zealand is nearly 40 years [1], it is considered that online condition monitoring of important transformers or transformers that have known issues is carried out to identify any incipient faults. The online condition monitoring in existing power transformers is hoped to minimize the risk of sudden failures and thereby prolong the in service life. It is equally important to decide on what to monitor in a power transformer and how to monitor, and these are also governed by the budgetary constraints. Transpower is in the process of acquiring online condition monitoring units for some of the new large power transformers it plans to purchase and will also retrofit such units to some old transformers as required. This paper presents the condition monitoring techniques currently used by Transpower on power transformers, and the online condition monitoring techniques for new and existing power transformers.en_US
dc.language.isoenen_US
dc.publishernternational Conference on Condition Monitoring and Diagnosis (CMD2010)en_US
dc.relation.ispartofseriesnternational Conference on Condition Monitoring and Diagnosis (CMD2010);pp. 239-242.-
dc.subjectpower transformers;condition monitoringen_US
dc.subjectdissolved gas analysis (DGA)en_US
dc.subjectonline gas monitorsen_US
dc.subjectRoger’s Ratioen_US
dc.subjectDuval Triangleen_US
dc.subjectwinding resistanceen_US
dc.subjectinsulation resistanceen_US
dc.subjecton load tap changers (OLTC)en_US
dc.subjectbushingsen_US
dc.titleCondition monitoring in New Zealand power transformersen_US
dc.typeArticleen_US
Appears in Collections:Research Papers - Department of Electrical and Electronic Engineering
Research Papers - SLIIT Staff Publications

Files in This Item:
File Description SizeFormat 
condition_monitoring_in_New_Zealand_power_transformers.pdf1.06 MBAdobe PDFView/Open