Publication:
A measurements-based discharge location algorithm for plain disc winding power transformers

dc.contributor.authorWang, Z. D
dc.contributor.authorHettiwatte, S. N
dc.contributor.authorCrossley, P. A
dc.date.accessioned2022-01-13T06:18:27Z
dc.date.available2022-01-13T06:18:27Z
dc.date.issued2005-06-20
dc.description.abstractA measurements-based electrical method for locating partial discharges (PD) in transformers is described in the paper. This location method relies on the series resonance frequencies of the signals produced at the transformer terminals by a discharge on the winding. Based on the equivalent circuit of plain disc type winding which consists of series inductance (L), series capacitance (K) and shunt capacitance to earth (C) of the winding, an analytical location algorithm is derived which gives the relationship between the location of a discharge and its terminal response's series resonance frequencies. LKC parameters of the equivalent circuit can be estimated using the series resonance frequencies of a calibration signal measured at the bushing tap during PD calibration. The PD location algorithm was tested on 11 kV transformer winding using signals produced by a discharge simulator and real discharges, and the results confirm its validity with a location accuracy of better than 10% of the winding length. However, blind area where this location algorithm is not applicable does exist near the neutral of the winding and far away from the measuring terminal. Since this location algorithm uses the series resonance frequencies below 500 kHz, it can be implemented with conventional PD measuring circuitry and instruments to detect and locate discharges in power transformers.en_US
dc.identifier.citationCited by 32en_US
dc.identifier.doi10.1109/TDEI.2005.1453445en_US
dc.identifier.issn1070-9878
dc.identifier.urihttps://rda.sliit.lk/handle/123456789/655
dc.language.isoenen_US
dc.publisherIEEEen_US
dc.relation.ispartofseriesIEEE transactions on dielectrics and electrical insulation;Vol 12 Issue 3 Pages 416-422
dc.subjectPower measurementen_US
dc.subjectPartial dischargesen_US
dc.subjectpower transformersen_US
dc.subjectpropagationen_US
dc.subjectwindingsen_US
dc.subjectbushing tapen_US
dc.titleA measurements-based discharge location algorithm for plain disc winding power transformersen_US
dc.typeArticleen_US
dspace.entity.typePublication

Files

Original bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
A_measurements-based_discharge_location_algorithm_for_plain_disc_winding_power_transformers.pdf
Size:
1.03 MB
Format:
Adobe Portable Document Format
Description:

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description: