Supervised Learning Approach to Infrared Image Based Condition Assessment of 33kV Lightning Surge Arresters

Thumbnail Image

Date

2025

Journal Title

Journal ISSN

Volume Title

Publisher

Institute of Electrical and Electronics Engineers Inc.

Abstract

This paper presents an online condition assessment method for 33kV Silicon rubber (SIR) housed ZnO surge arresters through infrared imaging. A total of 46 arrester samples including field-energized arresters, lab-tested arresters (field aged and a virgin arrester) were analyzed by infrared images and grouped into three "health"classes by laboratory measurements and modelling. Insulation resistance (IR) and leakage current (LC) measurements were taken for lab-tested arresters, whereas Finite Element Method (FEM) based modeling was used to assess field-energized samples. An infrared image consisted of 180 features and by Linear Discriminant Analysis (LDA), 180-dimensional thermal data were reduced to a 2D space with the three classification labels. Decision boundaries for classifying arresters were defined using Support Vector Machine (SVM), Random Forest (RF), and K-Nearest Neighbors (KNN) classifiers with their accuracy evaluated for effective arrester condition assessment.

Description

Keywords

Classifiers, Finite Element Method, Insulation Resistance, Leakage Current, Linear Discriminant Analysis

Citation

R. Illesinghe, M. Fernando and N. Paranawithana, "Supervised Learning Approach to Infrared Image Based Condition Assessment of 33kV Lightning Surge Arresters," 2025 IEEE 19th International Conference on Industrial and Information Systems (ICIIS), Peradeniya, Sri Lanka, 2026, pp. 506-510, doi: 10.1109/ICIIS69028.2026.11450750.

Endorsement

Review

Supplemented By

Referenced By